Water Source Heat Pump
Water Source Heat Pump

Water source heat pump

In air source systems, the climate difference of the place where it will be installed is taken into account, while in water source systems, it is sufficient to have a suitable water source. You can amortize your investment cost in the shortest time with a water source heat pump.

These are heat pumps produced with the latest advanced technology.

Water Source Heat Pumps provide economical and high efficiency.

Complete solution water source heat pumps that meet various needs; It offers heating, cooling and hot water supply solutions all year round.

Heat pumps are manufactured with low noise design.

Cooling or heating is a single It can be realized with a system; 50% cost reduction in investment equipment.

Water source heat pumps are environmentally friendly systems and do not harm the environment. In heating mode, you prevent smoke pollution with the heat pump, and in cooling mode, you can prevent the noise from the cooling tower with the heat pump.

Water source heat pumps obtain 5 KW heat power with 1 KW electrical power in winter months. In summer, it obtains 6KW cooling power with 1 KW electrical power. The efficiency of water source heat pumps is 3-4 times higher than electric heaters.

With water source heat pump without the need for a boiler and related equipment You can save space.

Water source heat pumps can be used in places such as residences, offices, hotels, banks, schools, stadiums and commercial buildings. It is suitable for places that require low noise levels, such as hospitals and hotels.


Technical Specifications

   ETW17W01TETW22W01TETW37W01TETW85W01T
HEATINGNominal Capacity*kW1721.637.582.6
Power DrawnkW3.44.17.218
COPW/W55.35.24 .6
Operating Temperature Range°C+5/+20+5/+20+5/+20+5/+20
Maximum Leaving Water Temperature°C55555555
COOLINGNominal Capacity**kW14.71932.371
Power DrawnkW33.76.414
EERW/W4.95.1455
Operating Temperature Range°C+15/+45+15/+45+ 15/+45+15/+45
Maximum Leaving Water Temperature°C7777
VoltageV/PH/Hz380/3/50380/3/50380/3/50380/3/50
Refrigerant R410AR410AR410AR410A
CompressorTypeSCROLLSCROLLSCROLLSCROLL
BrandPanasonicPanasonicPanasonicPanasonic
Quantity1112
Packaged DimensionsWidthmm7007007001200
Depthmm7007007001000
Heightmm1150115011501300
Weightkg145175275430
Net DimensionsWidthmm6306306301000
Depthmm600600600800
Heightmm1100110011001100
Weightkg120150250400
Circulation Pump Flowm³/h33315
Device Pressure LosskPa50505050
Circulation PumpBrandNONENONENONENONE
Inlet and Outlet Pipe Diametermm11 1/41 1/42
Cable Cross-Section max. Calculated for 10m lengthmm²5x2.55x45x45x6
FuseA3x10(NC-C)3x16(NC-C)3x25(NC-C)3x32(NC-C)
Room Control Cable Sectionmm²2 x 0.752 x 0.752 x 0.752 x 0 .75
*Device heating capacity is given according to the values ​​below.
Primary CircuitReturn10°C   
  Departure5°C   
Secondary CircuitReturn30°C   
  Departure35°C   
**Device cooling capacity is given according to the values ​​below.
Primary Circuit Return20°C   
  Departure25°C   
Secondary Circuit Return12°C   
  Departure7°C   
Get a Quote