Ground Source Heat Pump
Ground Source Heat Pump

Geothermal Heat Pump

The Ekotec geothermal heat pump uses free renewable energy from the ground. It is highly efficient with low operating costs and low carbon emissions. Our devices provide energy-efficient heating, cooling, and domestic hot water for residential and small commercial applications. The energy cost required for heating is reduced by 80% compared to other fossil fuels when using a geothermal heat pump.

These heat pumps are produced using advanced technology.

Geothermal heat pumps are economical and highly efficient.

The complete solution provided by the geothermal heat pump meets various needs; it offers heating, cooling, and hot water supply solutions throughout the year.

The heat pumps are designed with low noise levels.

Heating or cooling can be achieved with a single system; the investment cost in equipment is reduced by 50%.

Geothermal heat pumps are environmentally friendly systems that do not harm the environment. In heating mode, the heat pump prevents air pollution, and in cooling mode, the noise from the cooling tower can be prevented with the heat pump.

In geothermal heat pumps, 1 kW of electrical power generates 5 kW of heating power during winter. In summer, 1 kW of electrical power generates 6 kW of cooling power. The efficiency of geothermal heat pumps is 3-4 times greater compared to electric heaters.

With a geothermal heat pump, you can save space without the need for a boiler and related equipment.

Geothermal heat pumps can be used in residential homes, offices, hotels, banks, schools, stadiums, and commercial buildings. They are suitable for places like hospitals and hotels where low noise levels are required.

Product Technical Specifications

Model ETW17W01T ETW22W01T ETW37W01T ETW85W01T
Heating        
Nominal Capacity* kW 17 21.6 37.5
Power Consumption kW 3.4 4.1 7.2
COP W/W 5 5.3 5.2
Operating Temp. Range °C +5/+20 +5/+20 +5/+20
Max Outlet Water Temp. °C 55 55 55
Cooling        
Nominal Capacity** kW 14.7 19 32.3
Power Consumption kW 3 3.7 6.4
EER W/W 4.9 5.14 5
Operating Temp. Range °C +15/+45 +15/+45 +15/+45
Max Outlet Water Temp. °C 7 7 7
Voltage V/PH/Hz 380/3/50 380/3/50 380/3/50
Refrigerant   R410A R410A R410A
Compressor Type   SCROLL SCROLL SCROLL
Brand   Panasonic Panasonic Panasonic
Quantity   1 1 1
Packed Dimensions Width mm 700 700
  Depth mm 700 700
  Height mm 1150 1150
Weight kg 145 175 275
Net Dimensions Width mm 630 630
  Depth mm 600 600
  Height mm 1100 1100
Weight kg 120 150 250
Circulation Pump Flow m³/h 3 3 3
Device Pressure Loss kPa 50 50 50
Circulation Pump Brand   None None None
Pipe Inlet/Outlet Diameter mm 1 1 1/4 1 1/4
Cable Cross-Section (calculated for max. 10m length) mm² 5x2.5 5x4 5x4
Fuse A 3x10(NC-C) 3x16(NC-C) 3x25(NC-C)
Room Controller Cable Cross-Section mm² 2 x 0.75 2 x 0.75 2 x 0.75

*Heating capacity is provided according to the following values:

  • Primary Circuit Return: 10°C
  • Primary Circuit Supply: 5°C
  • Secondary Circuit Return: 30°C
  • Secondary Circuit Supply: 35°C

**Cooling capacity is provided according to the following values:

  • Primary Circuit Return: 20°C
  • Primary Circuit Supply: 25°C
  • Secondary Circuit Return: 12°C
  • Secondary Circuit Supply: 7°C
Get a Quote